Peaco support CJX2 AC contactor consists with optional auxiliary contacts, 24V/ 110V/ 220V coil, is mainly used at 50Hz - 60Hz operational frequency with maximum allowable rated voltage 380V and 690V for AC3 / AC4 type industrial application. AC contactor CJX2-1201 features 12A rated current and 3NO main contact and 1NC auxiliary contact. 3 pole/ 4 pole AC contactor with other currents are available.
AC Contactor Specifications
Model | PEACO-CJX2-12 | ||
Rated current* (optional) |
380V | AC-3 | 12A |
AC-4 | 5A | ||
660V | AC-3 | 9A | |
AC-4 | 2A | ||
Conventional heating current | 20A | ||
Rated insulation voltage | 690V | ||
Power of controllable 3-phase squirrel cage motor (AC-3) | 220V | 3kW | |
380V | 5.5kW | ||
660V | 7.5kW | ||
Operational frequency | Electric life | AC-3 | 1200 operations/h |
AC-4 | 300 operations/h | ||
Mechanical life | 3600 operations/h | ||
Service life | Electric life | AC-3 | 1,000,000 operations |
AC-4 | 200,000 operations | ||
Mechanical life | 10,000,000 operations | ||
Matching fusing model | RT16-20 | ||
Average power consumption at 50Hz, 20℃ | Pick-up | 76VA | |
Holding | 94VA | ||
Pole* (Optional) | 3P+NO, 3P+NC, 4P(4NO), 4P(2NO+2NC) | ||
Weight | 0.33kg | ||
Certification | CCC | ||
Warranty | 2 years |
Note: For electricity-related maintenance and installation, make sure that the operator holds the qualification for electrical work and takes necessary power-off and insulation protection measures.
Features
- 32 pieces of iron core with solid materials, the suction is more smooth and tight.
- Provides silver alloy contacts with strong conductivity and flame retardant housing.
- With copper coils with strong electromagnetic suction when the coil is energized.
Normal Working and Installation Conditions
1. Ambient temperature: -5℃~+40℃, the average value should not exceed +35℃ within 24 hours.
2. Altitude: <2000m.
3. Atmospheric conditions: When the temperature reaches 40℃, the relative humidity of atmosphere should be <50%. When at relatively low temperatures, it could have higher relative humidity. Monthly maximum relative humidity could be not more than 90%. Special measures should be taken if there is occurrence of dews due to temperature changes.
4. Class of pollution: Class 3
5. Installation category. Ⅲ
6. Installation conditions: The inclination degree between the installation surface and the vertical surface does not exceed ±5°.
7. Impact shock: AC contactors should be installed and used in the place where there are no strong shakes and impacts.
AC Contactor Dimension (Unit: mm)
Amax=47, Bmax=76, Cmax=82, Dmax=115, Emax=135, Fmax=73, a=35, b=50/60, Φ=4.5