- Stock: In Stock
- Model: PEACO-FC110-2S/4T-22G
- SKU: PEACO-STVFD-30
Available Options
30 hp single phase to 3 phase VFD is designed for constant torque motor, pump motor, and lift/ elevator motor, converting single phase 220V-240V input to three phase 320V-460V output. High-performance 30-hp variable frequency drive features built-in RS485 communication, and excellent vector control.
Our VFD are suitable for single-phase and split-phase input power supplies.
Navigation: Motor Controls > Variable Frequency Drives >1 Phase to 3 Phase VFD > 30 hp Single Phase to 3 Phase VFD
Specifications
Basic Features | Model | PEACO-FC110-2S/4T-22G |
Code | G: Constant torque, P: Pump motor | |
Rated capacity | 22kW | |
Rated input current | 176A | |
Rated output current | 45A | |
Input rated voltage | 220V 50/60Hz | |
Input rated frequency | 50/60Hz | |
Output rated voltage | 380V | |
Allowable output voltage range | 320V~460V | |
Output frequency | Vector control: 300 Hz, V/F control: 3200 Hz | |
Adoptable motor type* | Squirrel cage induction motor, asynchronous motor (Contact us for Permanent Magnet Motor) | |
Control Features | Control mode | Open-loop vector control (SVC), Closed-loop vector control (FVC), V/F control |
Input frequency resolution | Digital setting: 0.01 Hz, Analog setting: Maximum frequency*0.025% | |
Carrier frequency | 0.5 kHZ-16kHZ, Automatically adjusted based on load features. | |
Torque control/Steady speed accuracy | ±5%(FVC)/ ±0.5%>(SVC), ±0.02%(FVC) | |
Start-up torque | G-type: 0.5 Hz/150%, 0 Hz/180% (FVC), P type: 0.5Hz (FVC) | |
Overload capacity | G-type: 150% rated current 60 s, 180% rated current 3 s, P-type: 120% rated current 60s; 180% rated current 3 s | |
Ramp mode | Straight-line ramp or S-curve ramp, Four groups of acceleration /deceleration time with the range of 0.0s-6500.0s | |
DC braking | 0.00Hz - maximum output frequency, Braking time: 0.0s - 36.0s Braking action current value: 0.0% - 100.0%. | |
JOG control | JOG frequency range: 0.00Hz-50.00Hz, JOG acceleration / deceleration time: 0.0s-6500.0s | |
Build-in PID | Realizes process-controlled closed-loop control system easily. | |
Automatic voltage adjustment (AVR) | Maintain constant output voltage automatically when the main voltage changes. | |
Individualized Function | Safety self-inspection of power on peripheral equipment | Safety detection of peripheral equipment such as grounding, short circuits, and so on. |
Over-voltage and Over-loss speed control | Automatic limit of current and voltage during operation to prevent frequent over-current and over-voltage tripping | |
Fast current limit | Minimizing overcurrent fault and protecting frequency converter in normal operation | |
Common DC Bus function | Common DC bus functions of multiple frequency converters. | |
Quick key | User-defined shortcut menu | |
MF.K key | Programmable Key: Command channel Switching/forward and reverse running/JOG running function selection | |
Textile swing frequency control | Given the length control function | |
Timing control | Timing control function: setting time range 0h-65535hr | |
Running command sources | Running command sources | Three channels: operation panel, control terminal, and serial communication port. They can be switched over between these sources in various ways. |
Frequency sources | 10 frequency sources, such as digital setting, analog voltage setting, analog current setting, pulse setting, and serial communication port setting. They can be switched over these sources in various ways. | |
Auxiliary frequency command | 10 kinds of auxiliary frequency instructions. It can realize auxiliary frequency fine adjustment and frequency synthesis flexibly. | |
Input terminal | 7-Digital Input terminal, where X5 is compatible with high-speed pulse input. Suitable for PNP or NPN input mode. | |
2-Analog Input terminal 0-10V/0-20 mA. To be used as voltage or current input. | ||
Output terminal | 3-Digital output terminals and 2-Relay output terminals. | |
1-High speed output terminal DO, 0 kHZ-100 kHz square wave signal output, It can realize the set frequency, output frequency, and other physical quantities. | ||
2-Analog output terminal 0-10V/0-20 mA. To be used as voltage or current output. | ||
Display and keyboard | LED display | Display monitoring parameters, output frequency, set frequency, bus voltage, etc. |
Keyboard lock and function selection | To realize partial or total lock of keys, define the scope of action of some keys, to prevent mis-operation. | |
Protection function | Short circuit detection, input and output phase loss protection, overcurrent protection, overvoltage protection, under-voltage protection, overheat protection, and overload protection. | |
Brake unit | Build-in brake unit | |
Environment | Installation location | Indoor, free from direct sunlight, dust-free, corrosive gases, combustible gases, oil smoke, vapor, drip or salt, etc. |
Altitude | <1000m | |
Ambient temperature | < 95 % RH, no water droplet condensation | |
Humidity | -10°C~ +40°C (ambient temperature is 40°C-50°C , please de-rate to use) | |
Vibration | <5.9m/s 2 (0.6g) | |
Storage temperature | -20℃~+60℃ | |
IP level | IP20 | |
Pollution grade | PD2 | |
External Accessories* | Matched optional Brake resistance, input EMC filter, output EMC filter, input AC reactor, output AC reactor, energy regenerated reactor, harmonic filter, and sine wave filter (excluding VFD price). |
1. * denotes the parameters are optional or customized and please select every parameter in drop-down lists to complete your order.
2. Please contact us for the external accessories catalog and price.
30 hp VFD Dimension (Unit: mm)
A | H | D | W | B | Φ | Weight |
220 | 321 | 198 | 205 | 305 | Φ5.5 | 6.5kg |
KNOWLEDGE BASE
Can VFD be adjusted to 1Hz? What is the highest frequency that can be adjusted?If the VFD is used on a general AC asynchronous motor, its current is close to DC when the VFD is adjusted to 1Hz, which is absolutely impossible. The motor will work under the maximum current limited by the inverter, and the motor will generate huge heat, which will lead to burning the motor.
If the VFD operates at over 50Hz, it will suffer from more iron loss of the motor, which is also bad for the motor. Generally speaking, it is not recommended to exceed 60Hz (it is allowed to exceed 60Hz in a short time), otherwise it will also reduce motor life.