- Stock: In Stock
- Model: PEACO-CI19-32
- SKU: PEACO-CI19-32
Available Options
32A capacitor switching contactor features flame retardant enclosure, copper coil with good electrical conductivity and long service life. The auxiliary head is removable, making it suitable for different needs. 220V/380V coil rated voltage, 2 NO / 1 NO+ 1 NC / 2 NC auxiliary contact of AC contactor to choose. Reliable 3 phase AC contactor applied to improve the power factor in a circuit.
AC Contactor Specifications
Model: PEACO-CI19-32
Poles description: 3P
Controllable capacitor capacity: 9 Kvar (for 220V), 18 Kvar (for 380V)
Rated insulation voltage: 500V
Rated operational voltage: 220V/240V, 380V/400V (Optional)
Conventional thermal current: 32A
Rated working current AC-6b and 400VA: 23A
Prevention capacity on closing surge: 20le
Action condition: pull-in (85%-110%) Us, release (20%-75%) Us
Coil power (start/keep): 110/11 VA
Control supply voltage: 110V, 127V, 220V, 380V
Highest operating frequency (Time/hour): 120
Electrical life: 100, 000 times
Mechanical life: 1,000,000 times
Auxiliary contact composition: 2 NO (20), 1 NO+ 1 NC (11), 2 NC (02) (Optional)
Auxiliary contact control capacity: AC-15 360VA, DC-13 33W
Weight: 0.63kg
ApplicationFeatures
1. The AC contactor is equipped with a current-limiting resistor, which can suppress the closing inrush within the allowable range.
2. Capacitor switching contactor features a direct-acting double-breakpoint structure, with flexible action mechanism and compact structure, convenient to check manually and replace contacts.
3. The AC contactor terminals are covered with an insulating cover, which is safe and reliable.
4. The installation can be fastened with screws or it can be fastened on the 35 mm or 75 mm standard installation rail.
Environment
1. Ambient temperature: -5℃~+40℃, the average value should not exceed +35℃ within 24 hours.
2. Altitude: <2000m.
3. Atmospheric conditions: When the temperature reaches 40℃, the relative humidity of atmosphere should be <50%. When at relatively low temperatures, it could have higher relative humidity, such as relative humidity up to 90% at 20℃. Special measures should be taken if there is occurrence of dews due to temperature changes.
4. Class of pollution: Class 3
5. Installation category. Ⅲ
6. Installation conditions: The inclination degree between the installation surface and the vertical surface does not exceed ±5°.
7. Impact shock: AC contactors should be installed and used in the place where there are no strong shakes and impacts.