- Stock: In Stock
- Model: PEACO-FC280-4T-250G/280P
- SKU: PEACO-TVFD-250280
Available Options
350 hp (250 kW) VFD (variable frequency drive) features three-phase 220V, 380V, 440V, 460V, and 480V input/output voltage, providing controlled acceleration/deceleration to help extend the life of the AC motor. High-performance inverter to save energy and cost for your projects. Multiple control features such as V/f control, and close-loop vector control method makes it suitable for all kind of industrial application. Our VFD can be easily used to operate multiple identical motors simultaneously.
Navigation: Motor Controls > Variable Frequency Drives > Three Phase VFD > 350 hp (250 kW) VFD, 3 Phase 380V 440V 460V Input/ Output
Basics | Model | PEACO-FC280-4T-250G/280P | |
Rated Capacity | 350 hp (250 kW) | ||
Rated Input Current | 468A (for 380V) | ||
Rated Output Current | 465A (for 380V) | ||
Certification | CE | ||
Warranty | 12 months | ||
Applicable Motor Output | 250 kW | ||
Power | Input Rated Voltage* | 220V/380V/660V/1140V (-15%~+20%) & 460V/480V |
|
Output Rated Voltage* | 220V/380V/660V/1140V (-15%~+20%) & 460V/480V |
||
Rated Frequency | 1.0~3200Hz | ||
Robust Design | IGBT current > 2 times of inverter output current, Capacitor > 50uF/A | ||
PCB aging test | 100% test, 50°C, 12 hours. | ||
Finished products aging test | 100% test, 50°C, 24 hours. | ||
Control Feature | Control System | VF Control / Open Sensor Vector Control / Closed loop Vector (PG card) | |
Output Frequency Resolution | 0.1Hz | ||
Torque Characteristics | Including the auto-torque, auto-slip compensation, starting torque can be 0.5 Hz/150% (V/f), 1 Hz/150% (SVC),0 Hz/180% (FVC) | ||
Overload Endurance | 150% / 120s, 160% / 60s, 180% / 10s, 200% / 1s | ||
Acc / Dec Time | 0.1~65000s. (can be set individually) | ||
Torque Boost | Automatically torque boost, manually torque boost: 0.1%~30.0% | ||
Stall Prevention Level | 20~200%, setting of Rated Current | ||
Operating Feature | Input / Output Terminals | Keypad | Removable |
Input terminals | 6 multifunctional inputs, one can work as high-speed pulse Input. 3 programmable analog input: AI1, AI2, AI3: 0~10V / 4~20mA. |
||
Output terminals | 2 Groups relay outputs, 1 open collector outputs. 2 Analog outputs, 0~10V / 4~20mA. |
||
Communication Terminals | Build-in standard RS485 communication interface. MODBUS-RTU communication protocol. | ||
Built-in PID | Built-in PID control to easily realize the close loop control of the process parameters (such as pressure, temperature, flow, etc.) | ||
Jog Operation | Jog operation frequency: 0.0Hz~maximum frequency. Jog acceleration/deceleration time: 0.1s~3600.0s. | ||
Other Function | AVR, S-curve, Over-Voltage Stall Prevention, DC Braking, Fault Records, Adjustable Carried Frequency, Starting Frequency Setting of DC Braking, Over-Current Stall Prevention, Momentary Power Loss Restart, Reverse Inhibition, Frequency Limits, Parameter Lock/Reset. | ||
Protection | Over Voltage, Over Current, Under Voltage, Overload, Electronic Thermal, Overheating, Self-testing. | ||
Others | Including EMC Filter (C2/C3 Standard) | ||
Cooling | Forced air-cooling | ||
Installation | Altitude 1,000 m or below, keep from corrosive gasses, liquid, and dust. | ||
Ambient Temp | -10°C~+40°C (Non-Condensing and not frozen) | ||
Storage Temp | -20°C~+60°C | ||
Ambient Humidity | Below 90% RH (non-condensing) | ||
Vibration | 9.80665m/s2 (1G) less than 20Hz, 5.88m/s2 (0.6Gat) 20 to 50Hz | ||
External Accessories |
Matched optional input EMC filter, output EMC filter, input AC reactor, output AC reactor, energy regenerated reactor, harmonic filter, and sine wave filter (excluding VFD price). |
VFD Application in Fan and Pump
Variable frequency drive (VFD) can help fans and water pumps save energy. After the fan and pump load adopts VFD to regulate speed, the power saving rate is up to 20%~60%. Why can a VFD save much energy? This is because the actual power consumption of the fan and pump load is basically proportional to the cube of the rotation speed. When a small average flow is required, the user uses a frequency converter to decelerate the fan and pump, which can save energy obviously. However, the traditional fans and pumps use baffles and valves to adjust the flow, the motor speed is basically unchanged, and the power consumption does not change much.
- The first section of VFD (variable voltage control) not only converts the AC supply voltage into DC but also controls the required pulsating DC output voltage to maintain V/f constant ratio by using SCR/IGBT rectifier.
- The second section of VFD (DC-Link/DC Bus) consists of inductance and capacitors to convert pulsating DC into pure direct current. Here, inductance smooths the current, and the capacitor smooths the voltage.
- The third section of VFD (referred to as variable frequency control) not only converts DC voltage back into AC voltage but also controls the variable frequency to maintain the V/f ratio by using electronic devices such as SCR/IGBT transistors.
- Cooling method-forced air.
- Keep away the ac converter from corrosive gasses, liquid, moisture, and dust.
- Installation location altitude below 1000m (In the case above 1000m, VFD is to be de-rated. Please contact for technical support).
- Storage-temperate -20℃ to +60℃.
- Ambient temperature -10℃ to +40℃ (non-condensing and not frozen).
- Ambient humidity below 90% RH.
- Vibration under 20Hz 9.8m/s(1G), over 20Hz 5.88m/s (0.6G).
- V/f (volts per hertz) or V/hz control.
- V/f with encoder or closed loop V/f (PG card).
- Open loop vector control.
- Closed loop vector control (PG card).
- VFD capacity is to be sized more or equal to the sum of the capacity of all connected motors.
- The sum of the distance between the VFD and all connected motors should be less than 500m. Introduce an output load reactor to avoid motor failure due to voltage spikes, current surges, or harmonics.
- Install circuit breaker MCB or with extra protection MPCB between each motor and VFD.
- The voltage of each motor should be the same and ensure the VFD adoptable current is higher than the sum of all rated currents.
- Connect all motors with VFD output in parallel.